Technology guide, established

Direct liquid cooling (direct-to-chip)

Direct liquid cooling pumps coolant through cold plates mounted on CPUs, GPUs and other hot components, removing most server heat into liquid. It is the main route to rack densities beyond what air can handle, and it comes in single-phase water or glycol and two-phase refrigerant variants.

Also called: DLC, direct-to-chip, D2C, cold plate cooling, two-phase direct-to-chip

What it is

Cold plates sit on the hottest chips and a closed technology cooling loop carries the heat to a CDU. Remaining components still need some air cooling, so most halls are hybrid. Single-phase systems use treated water or water-glycol (often PG25). Two-phase systems (for example Accelsius NeuCool, ZutaCore HyperCool) boil a dielectric refrigerant at the cold plate and avoid water in the white space.

Where it fits

New AI halls and retrofits where rack density outgrows air. Vendors such as LiquidStack note that air cooling struggles beyond roughly 30 to 50 kW per rack. Treat such thresholds as vendor guidance, not a standard.

Sourcing considerations

The system crosses supplier boundaries: server OEM cold plates, rack manifolds, quick disconnects (for example UQD and MQD/MQDB couplings), CDU, and facility water. Agree who owns fluid quality, flushing, leak detection and warranty at each interface. Ask for wetted materials lists and coolant qualification. Negative pressure systems (Chilldyne) trade pump design for reduced leak risk.

Prototype vs shipping

Single-phase DLC with CDUs is commercially shipping from many vendors. Two-phase systems are shipping from some specialists (Accelsius MR250 is listed as a product) but have a smaller installed base. Treat new cold plate and connector standards (OCP MQD/MQDB specification approved Oct 2026) as emerging.

Questions to ask suppliers

  • Which party supplies and warrants cold plates, manifolds, quick disconnects and CDU
  • Approved coolant and fluid maintenance plan
  • Leak detection method and response
  • Facility water temperature class needed (ASHRAE W class)
  • Share of heat captured by liquid vs residual air
  • For two-phase: refrigerant type, GWP, regulatory status and refill logistics

Start a requirement brief

Suppliers with public evidence

Listed alphabetically. Inclusion means a public source shows the company offers products or services for this technology. It is not a ranking or endorsement. Compare these suppliers.

Projects using or planning it

Related news and analysis

Sources (7), last checked 18 Oct 2026
  1. Emergence and expansion of liquid cooling in mainstream data centers (opens in a new tab), ASHRAE TC 9.9, accessed 18 Oct 2026
  2. Water-cooled servers: common designs, components and processes (opens in a new tab), ASHRAE TC 9.9, accessed 18 Oct 2026
  3. MQD/MQDB OCP design specification 1.0.0 (opens in a new tab), Open Compute Project, published 2026-10, accessed 18 Oct 2026
  4. NeuCool MR250 (opens in a new tab), Accelsius, accessed 18 Oct 2026
  5. HyperCool (opens in a new tab), ZutaCore, accessed 18 Oct 2026
  6. Danfoss Hansen MQD/MQDB data sheet (opens in a new tab), Danfoss, accessed 18 Oct 2026
  7. CDU-1MW (air vs liquid FAQ) (opens in a new tab), LiquidStack, accessed 18 Oct 2026

Last checked 18 Oct 2026 by CoolPower Index research (automated, sourced). Report a correction.