Technology guide, established
Coolant distribution units (CDUs)
A CDU is the pump, heat exchanger and control skid that separates the facility water loop from the clean technology cooling system (TCS) loop feeding cold plates or immersion tanks. Ratings depend on approach temperature, flow and fluid, so capacities are only comparable at stated conditions.
Also called: CDU, CDUs, coolant distribution unit, cooling distribution unit, FDU, facility distribution unit, TCS, technology cooling system
What it is
A CDU moves heat from the IT-side loop (TCS) to the facility water system (FWS) through a plate heat exchanger. It controls supply temperature and flow, keeps the TCS above the dew point, filters the coolant and raises alarms on leaks, pressure or flow. Liquid-to-air units reject heat to room air instead and suit sites without facility water.
Form factors
In-rack units sit inside an IT rack and typically cover tens to low hundreds of kW. In-row units sit in the row and in 2026 commonly span about 0.6 to 2.5 MW. Facility or skid units sit in a gallery or plant room and are marketed from about 2.5 MW to beyond 8 MW per unit. Examples with published figures: Vertiv CoolChip CDU 70 to 2300 kW, Rittal CDU In-Row 1,000 kW at 4 K approach, DCX 8 MW FDU at 2 °C approach.
Why ratings are hard to compare
A capacity figure means little without approach temperature difference (ATD), flow per kW, fluid (water, PG25) and supply temperatures. The same Eaton ROL2300 is rated 2,300 kW at 8 °C approach and 1,150 kW at 4 °C. LiquidStack's CDU-1MW reaches 1,350 kW at 1.15 lpm/kW but 1,004 kW at 1.50 lpm/kW. Always normalise to the same ATD and lpm/kW.
Sourcing considerations
Check redundancy (N+1 pumps, 2N filters, dual power feeds), filtration grade (25 or 50 micron, side-stream 0.2 micron options), wetted materials and fluid compatibility, controls protocols (Redfish, Modbus, BACnet, SNMP), group control for many units, harmonics of pump drives, service access, factory test load, local service coverage and lead time. The Open Compute Project publishes the Project Deschutes facility specification as an open reference for CDU requirements.
Prototype vs shipping
Many 2025 to 2026 CDUs are announced before they ship. Examples in our records: Trane LiquidStack CDU 2.X is on pre-order with shipments from Q2 2027. nVent lists CX121 and CZ61/CZ62 on a 'coming in 2026' page. Supplier records mark each product family as prototype, announced, orderable or shipping, and unknown status stays unknown.
Questions to ask suppliers
- State capacity at a defined ATD, TCS flow per kW, fluid and FWS/TCS supply temperatures
- Pump redundancy and whether pumps and filters are hot-swappable
- Filtration grade on TCS and FWS sides
- Wetted materials list and approved coolants
- Control protocols and group control limits
- Electrical supply options, dual feed, harmonic mitigation
- Factory acceptance test load and witness options
- Commissioning, flushing and fluid sampling responsibility
- Local service presence and spares stock in the project country
- Lead time and current shipping status
Suppliers with public evidence
- Vertiv
- Schneider Electric
- Motivair by Schneider Electric
- CoolIT Systems
- LiquidStack
- DCX Liquid Cooling Systems
- Boyd
- nVent
- Rittal
- Stulz
- Trane
- Carrier
- Johnson Controls (York)
- Daikin Applied
- Mitsubishi Electric Hydronics & IT Cooling
- Airedale by Modine
- Modine
- Munters
- Alfa Laval
- Eaton
- Delta Electronics
- Envicool
- Accelsius
- ZutaCore
- JetCool
- Chilldyne
- Nortek Data Center Cooling
- Danfoss
- Kelvion
Listed alphabetically. Inclusion means a public source shows the company offers products or services for this technology. It is not a ranking or endorsement. Compare these suppliers.
Sources (8), last checked 18 Oct 2026
- Project Deschutes: data center facilities specification (opens in a new tab), Open Compute Project, published 5 Sept 2025, accessed 18 Oct 2026
- Vertiv CoolChip CDU 70-2300 kW (opens in a new tab), Vertiv, accessed 18 Oct 2026
- Coolant distribution unit (CDU) (opens in a new tab), Eaton, accessed 18 Oct 2026
- Rittal CDU In-Row 3343200 (opens in a new tab), Rittal, accessed 18 Oct 2026
- DCX 8 MW FDU (opens in a new tab), DCX, accessed 18 Oct 2026
- LiquidStack CDU-1MW sales literature (opens in a new tab), Trane Technologies, published 20 Apr 2026, accessed 18 Oct 2026
- Trane launches LiquidStack CDU 2.X (opens in a new tab), Trane Technologies, published 29 Sept 2026, accessed 18 Oct 2026
- nVent next generation liquid cooling (opens in a new tab), nVent, accessed 18 Oct 2026
Last checked 18 Oct 2026 by CoolPower Index research (automated, sourced). Report a correction.