CDU comparison guide

How to compare coolant distribution units fairly: which fields matter, why capacity only means something at a stated approach temperature, flow and fluid, and a table of published CDU data with every missing value marked not disclosed rather than guessed.

Why a CDU comparison needs rating conditions

CDU capacity depends on the approach temperature difference (ATD) between facility water in and technology coolant out, on TCS flow per kW and on the fluid. Published figures show how much this matters. Eaton rates one ROL unit at 2,300 kW with an 8 °C approach and 1,150 kW with 4 °C. LiquidStack rates its CDU-1MW between about 1,004 kW and 1,350 kW depending on flow per kW. Compare products only at the same ATD, flow per kW and fluid.

Fields to compare

Architecture (liquid-to-liquid or liquid-to-air). Location (in-rack, in-row, facility or skid). Capacity with ATD, flow per kW, fluid and supply temperatures. Flow and available pressure. Pump and filter redundancy. Filtration grade. Fluid compatibility and wetted materials. Controls protocols and group control. Footprint and weight. Electrical supply. Product status (prototype, announced, orderable, shipping). Regional service in the project country.

How to read the table

Rows come straight from published supplier records on this site, each linked to its source. Where a field is blank on the supplier's own page it reads not disclosed. A missing value is not a weakness of the product, only a gap in public information, so ask the supplier. Status reflects the supplier's own wording on the date checked.

Normalising quotes

Ask every bidder to state capacity at one agreed point, for example 4 °C ATD, 1.5 lpm/kW, PG25 TCS, with your facility water temperature. Ask for pump power at that point and for part load curves. Check whether quoted capacity assumes N or N+1 pumps running.

What we could not verify

For most products, fluid compatibility lists, certifications and evidence of service teams in specific countries were not published. Several new models are announced but not yet shipping. The supplier pages are the authority and may change.

Technologies

Sources (28), last checked 18 Oct 2026
  1. Airedale by Modine CDU product source (opens in a new tab), Airedale by Modine, accessed 18 Oct 2026
  2. Alfa Laval CDU product source (opens in a new tab), Alfa Laval, accessed 18 Oct 2026
  3. Eaton CDU product source (opens in a new tab), Eaton, accessed 18 Oct 2026
  4. Carrier CDU product source (opens in a new tab), Carrier, accessed 18 Oct 2026
  5. Daikin Applied CDU product source (opens in a new tab), Daikin Applied, accessed 18 Oct 2026
  6. CoolIT Systems CDU product source (opens in a new tab), CoolIT Systems, accessed 18 Oct 2026
  7. DCX Liquid Cooling Systems CDU product source (opens in a new tab), DCX Liquid Cooling Systems, accessed 18 Oct 2026
  8. DCX Liquid Cooling Systems CDU product source (opens in a new tab), DCX Liquid Cooling Systems, accessed 18 Oct 2026
  9. Delta Electronics CDU product source (opens in a new tab), Delta Electronics, accessed 18 Oct 2026
  10. Delta Electronics CDU product source (opens in a new tab), Delta Electronics, accessed 18 Oct 2026
  11. Envicool CDU product source (opens in a new tab), Envicool, accessed 18 Oct 2026
  12. JetCool (Flex) CDU product source (opens in a new tab), JetCool (Flex), accessed 18 Oct 2026
  13. Johnson Controls (York, Silent-Aire) CDU product source (opens in a new tab), Johnson Controls (York, Silent-Aire), accessed 18 Oct 2026
  14. Kelvion CDU product source (opens in a new tab), Kelvion, accessed 18 Oct 2026
  15. LiquidStack (Trane Technologies) CDU product source (opens in a new tab), LiquidStack (Trane Technologies), accessed 18 Oct 2026
  16. LiquidStack (Trane Technologies) CDU product source (opens in a new tab), LiquidStack (Trane Technologies), accessed 18 Oct 2026
  17. Mitsubishi Electric Hydronics & IT Cooling Systems CDU product source (opens in a new tab), Mitsubishi Electric Hydronics & IT Cooling Systems, accessed 18 Oct 2026
  18. Motivair by Schneider Electric CDU product source (opens in a new tab), Motivair by Schneider Electric, accessed 18 Oct 2026
  19. Munters CDU product source (opens in a new tab), Munters, accessed 18 Oct 2026
  20. Nortek Data Center Cooling CDU product source (opens in a new tab), Nortek Data Center Cooling, accessed 18 Oct 2026
  21. Nortek Data Center Cooling CDU product source (opens in a new tab), Nortek Data Center Cooling, accessed 18 Oct 2026
  22. nVent CDU product source (opens in a new tab), nVent, accessed 18 Oct 2026
  23. Rittal CDU product source (opens in a new tab), Rittal, accessed 18 Oct 2026
  24. Schneider Electric CDU product source (opens in a new tab), Schneider Electric, accessed 18 Oct 2026
  25. STULZ CDU product source (opens in a new tab), STULZ, accessed 18 Oct 2026
  26. Trane (Trane Technologies) CDU product source (opens in a new tab), Trane (Trane Technologies), accessed 18 Oct 2026
  27. Vertiv CDU product source (opens in a new tab), Vertiv, accessed 18 Oct 2026
  28. Project Deschutes facilities specification (opens in a new tab), Open Compute Project, published 5 Sept 2025, accessed 18 Oct 2026

Last checked 18 Oct 2026 by CoolPower Index research (automated, sourced). Report a correction.