Technology guide, established
Warm-water cooling loops
Warm-water loops run facility water at 30 to 45 °C or more so that heat can be rejected with dry coolers for most of the year and reused more easily. ASHRAE TC 9.9 defines W classes by maximum facility water supply temperature, from W17 up to W45 and W+ above 45 °C.
Also called: warm water cooling, W32, W40, W45, W+, ASHRAE W classes, high temperature facility water
What it is
Liquid cooled chips tolerate much warmer coolant than air cooled rooms need. Raising facility water temperature cuts or removes chiller hours and raises the grade of recovered heat.
ASHRAE classes
ASHRAE TC 9.9 uses classes W17, W27, W32, W40, W45 and W+, each named after the maximum facility water supply temperature in °C. Equipment claiming a class should run unthrottled across that range. Use the class to align IT, CDU and plant designs.
Examples
STULZ rates its CyberCool CDU at 32 °C facility water and 36 °C TCS supply. Trane's LiquidStack CDU 2.X supports facility inlet up to 45 °C. DCX designs its 8 MW FDU for 45 °C warm water operation.
Sourcing considerations
Warmer water needs a smaller CDU approach temperature to keep chips within limits, which means larger heat exchangers. Confirm the IT vendor's allowed TCS temperature, and agree who carries the risk if a future GPU generation needs colder water.
Questions to ask suppliers
- Target ASHRAE W class and why
- Approach temperature the CDU must achieve at that class
- IT vendor maximum TCS supply temperature
- Chiller backup hours and trim strategy
- Heat reuse offtake temperature
Suppliers with public evidence
Listed alphabetically. Inclusion means a public source shows the company offers products or services for this technology. It is not a ranking or endorsement. Compare these suppliers.
Relevant policy
Sources (5), last checked 18 Oct 2026
- Emergence and expansion of liquid cooling in mainstream data centers (opens in a new tab), ASHRAE TC 9.9, accessed 18 Oct 2026
- Thermal Guidelines 5th edition reference card (opens in a new tab), ASHRAE, accessed 18 Oct 2026
- CyberCool CDU (opens in a new tab), STULZ, accessed 18 Oct 2026
- LiquidStack CDU 2.X (opens in a new tab), Trane Technologies, published 29 Sept 2026, accessed 18 Oct 2026
- DCX announces new 8MW CDU (opens in a new tab), DCX, published 2026, accessed 18 Oct 2026
Last checked 18 Oct 2026 by CoolPower Index research (automated, sourced). Report a correction.