ToneCooling publishes measured datasheets for GB300 and GB200 direct-to-chip cold plate kits: about 1,067 W per GPU plate at 1.7 L/min
What changed
Chinese cold plate maker ToneCooling published datasheets for two standard direct-to-chip kits on 11 November. In the company's own steady-state test with pure water, each GPU cold plate in its GB300 NVL72-class tray kit removed 1,066.94 W at 1.7 L/min with a 12.06 kPa pressure drop and a thermal resistance of 0.0130 to 0.0133 °C/W; each CPU plate removed 485.46 W at 0.7 L/min. The GB300 kit is designed for 800 to 1,200 W per GPU, pure water or PG25, a 20 to 30 °C inlet and up to 3 bar, and a full NVL72 rack uses 18 kits; the GB200 kit is rated 1,200 W + 1,200 W + 300 W and a rack uses 36. These are manufacturer test results, not independent measurements. The company quotes 4 to 6 weeks for samples and 6 to 8 weeks for production.
View original source (opens in a new tab)
Read the original: ToneCooling (press release): ToneCooling publishes measured datasheets for GB300 and GB200 direct-to-chip cold plate kits: about 1,067 W per GPU plate at 1.7 L/min (opens in a new tab)
We summarise in our own words and link the source. Figures are as reported by the source and not independently verified. Report a correction.
Related index data
A supplier link means the company is named in the story or offers this kind of product. It does not mean a contract unless the story says so.
Related on CoolPower Index: Chip power and cooling.
More in CDUs & Direct Liquid Cooling
- ZTE launches a 1.5 MW cold plate liquid cooling CDU, expandable to 2.4 MW, alongside 800 V DC power for AI data centres 10 Nov 2026
- India's National Stock Exchange installs direct-to-chip liquid cooling for its own AI servers, planned to scale to 224 GPUs 9 Nov 2026
- Equinix opens SG6, Singapore's first data centre built under the stricter DC-CFA green rules, with a 1.20 PUE design target and liquid cooling 6 Nov 2026